TS-400\1250-1
| General information | ||
|---|---|---|
| Equipment type: | Oil cooler | |
| Subtype: | TS type oil cooler | |
| Alternative names: | Ц-400\1250-1-Н-УХЛ4; Ц-400\1250-1-М5-УХЛ4; Ц-400\1250-1-М5-Т4; Ц-400\1250-1-Н-Т4 | |
| Description for TS-400\1250-1 |
|---|
| Vertical TS type oil coolers are designed for dielectric oil water cooling. These oil coolers are widely used with power, furnace or general-purpose transformers. |
| Characteristics | ||
|---|---|---|
| Water resistance: | 0.025 | Mpa |
| Water operating pressure: | 0.3 | Mpa |
| Input water temperature: | 25 | °С |
| Water consumption: | 35 | m3/h |
| Oil operating pressure: | 0.4 | Mpa |
| Oil-water temperature difference: | 40 | °C |
| Oil consumption: | 100 | m3/h |
| Heat transfer: | 400 | kW |
| Dimensions* | ||
|---|---|---|
| Height (H): | 1875 | mm |
| Body diameter: | 340 | mm |
| Weight (empty): | 310 | kg |
| Overall drawing TS-400\1250-1 * |
|---|
|
help_oprosnik