| Description for DKVr-20-23-270GM |
|
Steam boilers of this type are designed for production of saturated or overheated steam which can be used within the frames of a wide range of industries, construction facilities, municipal engineering, power production, agricultural facilities and other sectors of national economy. These two-drum, watertube boilers have natural-circulation.
|
|
|
Technical data
|
| Capacity: |
20
t/h |
| Output pressure: |
2.3
MPa (kgf/cm2) |
| Output steam temperature: |
370
C |
| Feed water temperature: |
100
°C |
| Efficiency: |
91,6/89,5
% |
| Fuel consumption?: |
1560/ 1485
kg/h |
| Dimensions: |
5350x3214x3992/ 5910x3220x2940/ 5910x3220x3310
mm |
| Weight?: |
48681
kg |
|
|
Components
|
| Economizer / Air-heater: |
БВЭС-V-1 (ЭБ-1-808И) / ВП-О-228
|
| FD Fan: |
FDFB-12.5-1000
|
| ID Fan: |
IDFB-13-1500
|
| Burner: |
ГМГ-5 (3 шт: 2-лев., 1-прав.)
|
| Combustion chamber: |
н/д
|
| Pump: |
н/д
|
| Control type: |
н/д
|
| Other equipment: |
н/д
|
|