Backward curved blades. Running wheel on the electric motor shaft.
IDFB-12.5-1500
Description for IDFB-12.5-1500
Single inlet centrifugal ID Fans are intended to be used for flue gas removal from combustion chambers of solid fuel or gas-and-oil-fired boilers equipped with dry ash catchers. It is allowed to install such ID Fans in processing systems for handling compatible gases (The dustiness should be not more than 2 g/m3, abrasion and sticking tendency should be similar to ashed flue gases). Such ID Fans can be applied for single or serial-parallel operation. Double inlet centrifugal ID Fans can have right-hand or left-hand rotational direction. The right-hand rotation is in a clockwise order and it should be defined at electric motor side. The blades of impeller are backward curved.
Aerodynamic characteristics
Capacity:
39.9
ths. m3/h
Total pressure:
3510
Pa
Dimensions*
Length (L):
1745
mm
Width (W):
2236
mm
Height (H):
2040
mm
Weight:
1330
kg
Electric motor
Actuator power?:
75
kW
Rotation frequency:
1500
rpm
Moment of inertia:
35,12
kg*m2
Overall drawing IDFB-12.5-1500 *
* Dimensions may vary depending on the electric motor model, customer requirements and design constraints.